HVAC TOOLS
REFRIGERANT RECOVERY & RECLAIM
ECOsaver R11
- Made-to-order
- Low pressure refrigerant
- R11 vapor recovery 300g/min
- R11 push pull recovery 45,000g/min
For recovery of low pressure refrigerant from chiller system
SPECIFICATIONS
Item | ECOSAVER R11 |
---|---|
Code No. | ESR11 |
Applicable refrigerant | R11, R113, R123, R514A, HFO-1233zd |
Recovery method | Compressed vapor recovery method/Push-pull method |
Recovery rate | R11 vapor recovery: 300g/min R11 push pull recovery: 45,000g/min |
Voltage | single-phase 200V(50/60Hz) |
Compressor | 1500W 2 piston open drive (oil in) |
Weight | 96kg |
Operating temperature | 0~40°C |
Ultimate vacuum | -0.098MPa(-735mmHg) |
Applicable cylinder | RECOVERY CYLINDER WITH FLOAT SENSOR (3/4"port) Drum for refrigerant (※cannot recover R245fa to a drum) |
Standard accessories | FILTER FOR R11, 3/4"HOSE 6m, 3/4"HOSE 3m 2pcs, 3/4"BALL VALVE 4pcs, SAFETY CABLE, HOSE ADAPTER FOR WATER COOLING CONDENSER 2pcs |
Please contact us when recovery both of R245fa, R1224yd and R11, R113, R123, HFO-1233zd.